DefinitionDocument stating the normal and maximum consumption of e.g. diesel oil, compressed air, heating/cooling media etc., for the equipment(-s) or unit(-s).The following generalised index shall be used:• Equipment tag no.• Type of consumption• Normal Mode - The mode of platform operation when main process, utility systems (including drilling)and other facilities are in operation. This mode of operation gives the peak powerrequirement.• Critical Mode - The mode of platform operation just after a generator shut down and only one generator is running.• Stabilized Mode - The same mode of platform operation as mode B, but the situation is stabilized.• Emergency Mode - The mode of platform operation when main process, utility systems, supplies to existing facilities are shut down.- The main generators are shut down.- The emergency generator is running.The load list shall show individual consumers to high and low voltage switchboards.