DIRECT_AXIS_SHORT_CIRCUIT_TRANSIENT_TIME_CONSTANT

Download

Definition

The direct-axis transient short-circuit time constant (Td’) is the time, in seconds, required for the transient alternating component of the short-circuit current (line C) to decrease to 1/e, or 0.368, times its initial value.